JV3 or Deemed-to-Satisfy: which Section J route?

Most projects use Deemed-to-Satisfy. The J1V3 reference building method, still called JV3 from its 2019 name, models the whole building instead and trades one element against another.

Glass office facade with a tree and the sun

Two ways to meet the same requirement.

Under Part A2 of the NCC, Performance Requirements are met by a Deemed-to-Satisfy Solution (A2G3), a Performance Solution (A2G2), or a combination of the two (A2G4). For energy efficiency, the requirement in question is J1P1.

Deemed-to-Satisfy: follow the rules element by element.

A2G3 says a solution that complies with the Deemed-to-Satisfy Provisions is deemed to have met the Performance Requirements. For Section J, J2D1 lists the clauses, and J2D2 says a Class 3 to 9 building meets J1P1 by complying with Parts J4 to J8, J9D3 and J9D5(2) to (4).

Each element is checked against its own limit: roof and wall R-Values, glazing through Specification 37 for J4D6, sealing, plant efficiency, lighting power and controls. No whole-building model is needed.

J1V3: model the building against a reference.

J1V3, titled verification using a reference building, is a Verification Method, so it is used as part of a Performance Solution. It was JV3 in NCC 2019, became J1V3 in NCC 2022 and keeps that number in NCC 2025.

The proposed building is modelled and compared with a reference building based on the Deemed-to-Satisfy Provisions. Under NCC 2025 J1V3, compliance needs all of the following:

  1. Annual greenhouse gas emissions of the proposed building not more than 97% of the reference building's, modelled with the proposed services.
  2. With the reference building's services, the proposed building's emissions not more than the reference's, which tests the envelope on its own.
  3. Thermal comfort and zone load limits set out in the clause, which vary by climate zone.
  4. The additional requirements in Specification 33.
  5. A calculation method complying with ANSI/ASHRAE Standard 140, Specification 34 and Specification 48.

What changed between 2022 and 2025.

Under NCC 2022, J1V3 asked for emissions not more than the reference building's. NCC 2025 adds a 3% margin and adopts new weather files, as the ABCB summarises.

When each route makes sense.

Deemed-to-Satisfy suits most jobs

Fitouts, warehouses, small offices and shops where the elements can meet their limits. It is quicker to document and easier for the building surveyor to check.

J1V3 earns its time when one element cannot pass

A heavily glazed facade or a design the architect will not change. Modelling can show the building as a whole performs, letting better plant or lighting carry a facade that fails on its own.

The trade-off

J1V3 needs full energy modelling, the Performance Solution process under A2G2, and a building surveyor willing to accept it. It is a bigger job than Deemed-to-Satisfy.

We write Deemed-to-Satisfy Section J reports. Where a design cannot pass element by element, we say so early, so the team can choose between a specification change and modelling.

Sources: NCC 2025 Volume One, Part A2, Part J1, Part J2 and Specification 37; NCC 2022 Part J1; ABCB, NCC 2025 commercial energy efficiency changes and NCC 2022 lexicon. General information, not an assessment of any particular site.

The ones that come up every week.

Not sure your design passes Deemed-to-Satisfy? Send the plans.

Section J reports for Class 3 and 5 to 9 buildings in Victoria. Send the drawings and window schedule, and a quote comes straight back.

Common questions

Is JV3 the same as J1V3?

Yes.

The reference building method was JV3 in NCC 2019 and was renumbered J1V3 in NCC 2022.

NCC 2025 keeps J1V3, with a 3% margin and new weather files.

Is J1V3 a Deemed-to-Satisfy route?

No.

It is a Verification Method, used to show a Performance Solution meets J1P1.

Deemed-to-Satisfy means complying with the provisions in Parts J4 to J9 as listed in J2D2.

Can J1V3 let a facade fail the glazing limits?

It can, if the whole building still meets the emissions, comfort and load tests against the reference building.

The envelope test with reference services still has to pass.

Which route is quicker?

Deemed-to-Satisfy.

J1V3 needs whole-building energy modelling and the Performance Solution documentation process.

Need a Section J report?

For builders, developers and architects with a Class 3 to 9 building: NCC 2025, 2022 or 2019, within 72 hours.

Which reports does my job need?

The usual list, from each council’s planning scheme and website.

1. What are you building?
3. What stage are you at?

Tell us about the project.

A quick quote from your plans, before any work starts.

Quick quote from your plans. Planning and residential reports within 48 hours; Section J, CMP and GTP within 72 hours.

Start here

See which reports your job needs, then get the quote for that list.

Call 0470 389 168

Request a quote

Your name, email and the report you need. Add the drawings now or later.

Your details

Report type
Add details (optional)
NCC edition, if known
Which pathway does it need
What will it cost?
A quick quote from your plans, before any work starts.
Will council accept it?
Every report is written to the council’s own policy or the NCC edition that applies.